i750

The i750 cabinet servo inverter provides everything for precise and dynamic motion control in complex multi-axis applications. Advanced safety functions and One Cable Technology reduce wiring and control complexity. Intelligent data-based functions and IIoT enable innovative motion control concepts.
As a single or double axis, the i750 cabinet with a matching supplier fits seamlessly into the Lenze automation system. The strengths of the inverter become apparent in numerous applications in combination with Lenze controllers and the FAST Application Software Toolbox. The scalable range of hardware, software, engineering services, and digital services supports the realization of integrated automation systems from the cloud to the drive shaft.
As a power extension of the i750 cabinet servo inverter in the range of 22 ... 110 kW, the i950 cabinet servo inverter can be used.

Highlights

  • Integrated DC-bus connection
  • Small overall width from 50 mm for the double axis
  • Axis modules capable of multiple overloads for peak output currents between 5 and 64 A, double axes up to 32 A
  • Integrated Functional Safety and One Cable Technology (OCT)
  • Autotuning function for quick and easy controller adjustment
Obrázek
    Title File Document type Version
    Brochure i750 cabinet servo inverter Brochure 07/2025
    Flyer i750 cabinet servo inverter EN Flyer 03/2023
    Fault ID: 12816
    Hex: 0x3210
    Description: Fault - DC bus overvoltage
    Keypad display: DC Bus OV
    Cause Remedy Severity/response

    DC-bus voltage has exceeded the error threshold for overvoltage due to a too high braking energy or a too high mains voltage. The error threshold (display in 0x2540:006 (P208.06) results from the setting of the rated mains voltage in 0x2540:001 (P208.01).

    Reduce dynamic performance of the load profile.

    Check mains voltage.

    Check settings for brake energy
    management.

    0x2541:001 (P706.01) = [0]: Connect brake resistor to the power unit and activate the integrated brake chopper

    Fault

    Fault ID: 12672
    Hex: 0x3180
    Description: UPS operation active
    Keypad display: UPS oper. active
    Cause Remedy Severity/response

    Operation on uninterrupted 1x230V current supply (UPS) has been activated: Only a reduced output current is provided.

    Switch back to operation with regular mains voltage

    Warning

    Fault ID: 12576
    Hex: 0x3120
    Description: Mains phase fault 
    Keypad display: Mains Phase fail
    Cause Remedy Severity/response

    Mains phase failure

    • Check wiring of the mains connection.
    • Check fuses.

    Fault

    Fault ID: 1030
    Hex: 1030
    Description: Undervoltage in the DC bus
    Keypad display: LU
    Cause Remedy Severity/response

    DC bus voltage is lower than specified in C0173.

    • Check mains voltage
    • Check supply cable

    cawc

    Fault ID: 1020
    Hex: 1020
    Description: Overvoltage in DC bus
    Keypad display: OU
    Cause Remedy Severity/response

    Braking energy is too high. (DC−bus voltage is higher than set in C0173.)

    • Use braking unit or regenerative module.
    • Check dimensioning of the brake resistance.