Ugrás a tartalomra

i550

i550 cabinet frequency inverter

The i550 cabinet frequency inverter is a compact control cabinet device with scalable functionality. It is versatile, reliable, and easy to use.
The requirements of the Ecodesign Directive, Standard EN IEC 61800-9-2, are met.
Application areas: Conveyor drives, traveling drives, winding drives, hoist drives, extruders, packaging machines, pumps, fans, ...

Highlights

  • Space saving design: 60 mm wide (up to 4 kW), 130 mm deep (up to 11 kW), with zero-clearance mounting
  • Innovative interaction (e.g. over WLAN) makes new record-breaking commissioning times and convenient diagnostics a reality
  • Optionally available with "Safe Torque Off (STO)" with SIL 3 (EN IEC 61508) and Performance Level e (EN ISO 13849-1)
  • For the greatest possible flexibility available as a complete device or in individual parts (Power Unit, Control Unit and Safety Unit)
Kép
    Title File Document type Version
    Flyer i5xx cabinet frequency inverter EN Flyer 01/2025
    Fault ID: 0016
    Hex: 0016
    Description: I2xt overload
    Keypad display: OC6
    Cause Remedy Severity/response
    • Frequent and too long acceleration processes with motor overcurrent.
    • Permanent motor overload with Imotor >Irmotor

    Check drive dimensioning.

    Fault ID: x018
    Hex: x018
    Description: I2xt overload advance warning
    Keypad display: OC8
    Cause Remedy Severity/response
    • Frequent and too long acceleration processes with motor overcurrent.
    • Permanent motor overload with Imotor >Irmotor

    Check drive dimensioning.

    Fault ID: 0015
    Hex: 0015
    Description: I x t overload
    Keypad display: OC5
    Cause Remedy Severity/response
    • Frequent and too long acceleration with overcurrent
    • Continuous overload with Imotor > 1.05 x Irx

    Check drive dimensioning.

    Fault ID: 0012
    Hex: 0012
    Description: Motor cable earth fault
    Keypad display: OC2
    Cause Remedy Severity/response

    One of the motor phases has
    earth contact.

    • Search for cause of short circuit.
    • Check motor cable.
    Fault ID: 0011
    Hex: 0011
    Description: Short circuit of motor cable
    Keypad display: OC1
    Cause Remedy Severity/response

    Short circuit

    Excessive capacitive charging
    current in the motor cable.

    • Search for cause of short circuit.
    • Check motor cable.

      Use motor cable which is shorter
      or of lower capacitance.