i510 protec
The i510 protec frequency inverter uses the same tried-and-tested technology used in our control cabinet inverters. It only differs in terms of an adapted design. If there is not enough space in the control cabinet or the inverter has to be mounted directly on the motor in various machine modules, then this versatile and reliable device is the right solution.
The requirements of the Ecodesign Directive, Standard EN IEC 61800-9-2, are met.
Application areas: Conveyor drives, traveling drives, pumps, fans, ...
Highlights
- Versions with keypad, USB module or WLAN module for easy commissioning
- Industry standard fieldbus network options
Documentation
Error codes
| Cause | Remedy | Severity/response |
|---|---|---|
DC-bus voltage has exceeded the error threshold for overvoltage due to a too high braking energy or a too high mains voltage. The error threshold (display in 0x2540:006 (P208.06) results from the setting of the rated mains voltage in 0x2540:001 (P208.01). |
Reduce dynamic performance of the load profile. Check mains voltage. Check settings for brake energy 0x2541:001 (P706.01) = [0]: Connect brake resistor to the power unit and activate the integrated brake chopper |
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
Operation on uninterrupted 1x230V current supply (UPS) has been activated: Only a reduced output current is provided. |
Switch back to operation with regular mains voltage |
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
Mains phase failure |
|
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
DC bus voltage is lower than specified in C0173. |
|
cawc |
| Cause | Remedy | Severity/response |
|---|---|---|
Braking energy is too high. (DC−bus voltage is higher than set in C0173.) |
|