Remedy
Check and correct the assignment of the triggers to the functions.
- With keypad or network control, the two "Enable inverter 0x2631:001 (P400.01)" and "Run 0x2631:002 (P400.02)" functions can also be set to "Constant TRUE [1]" to start the motor.
Cause
The assignment directives have not been observed.
- If the "flexible I/O configuration" is active as control source, the "Enable inverter" or "Run" function must be connected to a digital input in order that the motor can be stopped again any time!
- The use of the "Start forward (CW)" and "Start reverse (CCW)" functions excludes the use of the "Run forward (CW)" and "Run reverse (CCW)" functions, and vice versa.
Description
Trigger/functions connected incorrectly
Keypad display
P400 config err
Severity/response
Trouble
Product categories