Skip to main content

0x81A1

Remedy
  • Check communication with the master.
  • Check wiring.
  • Check bus termination.
Cause

No valid messages have been received via the Modbus for a longer time than the time-out time set in 0x2858:002 (P515.02).

Description

Modbus: network time-out

Keypad display

Modbus time-out

Fault message ID
33185
Severity/response

Fault (configurable)

Severity/response - 2

Setting parameters: 0x2858:001 (P515.01)