Remedy
- Check wiring between inverter and motor.
- In case of a false tripping, adapt the settings for the motor phase failure detection. - 0x2D45:002 (P310.02) (Current threshold) - 0x2D45:003 (P310.03) (Voltage threshold)
Cause
A failure of the motor phase V has been detected.
Description
Motor phase failure phase V
Keypad display
Phase V failure
Severity/response
No response (configurable)
- The event can only be reset after a blocking time. Setting parameters: 0x2D45:001 (P310.01)
Severity/response - 1
Blocking time: 2 s