Skip to main content

0x2A006394

Remedy

After transferring an application with the "Application Loader", the release information for the safe parameter set must be generated separately for each device with the »EASY Starter« or »PLC Designer« via the +Safety parameter list+ and transferred to the device. After transmission, the safe parameter set must be saved in the device using the "Save" command.

Cause

No release information is available on the memory module.

Description

Memory module release information - access error

Fault message ID
704668564
Severity/response

Information