The i650 motec frequency inverter for wall mounting and motor mounting in protection class IP66 (UL Type 4X indoor) is the optimal decentralized drive solution. The inverter can be extended for universal use with an extension box with disconnect switch with/without Type E combination motor controller and operating elements.
The i650 motec frequency inverter stands out from the i550 motec due to its extended range of functions: For simple automation tasks, a logic PLC based on CODESYS in accordance with the IEC 61131-3 standard is integrated in the i650 motec. Table positioning is available for the realization of independent axes and machine modules. The “Extended Safety“ option (safety technology with various functions) rounds off the overall package.
The requirements of the Ecodesign Directive, Standard EN IEC 61800-9-2, are met.
Application areas: Conveyor drives, traveling drives, winding drives, hoist drives, extruders, packaging machines, pumps, fans, ...
Highlights
- Compact solution for decentralized drive technology, wall-mounted or motor-mounted, with high protection class IP66 (UL Type 4X indoor)
- Wall-mounted expandable: Extension box with disconnect switch with/without Type E combination motor controller and operating elements
- Fast mounting due to pluggable, standardized connections (plug & play)
- Four IO-Link ports with limited IO-Link master functionality for easy data exchange between IO-Link sensors and actuators
- Integrated regenerative module for very high energy efficiency - a brake resistor is no longer required
- Extended range of functions:
Logic PLC
Table positioning
"Safe Torque Off (STO)" via CIP Safety
Documentation
Error codes
| Cause | Remedy | Severity/response |
|---|---|---|
DC-bus voltage has exceeded the error threshold for overvoltage due to a too high braking energy or a too high mains voltage. The error threshold (display in 0x2540:006 (P208.06) results from the setting of the rated mains voltage in 0x2540:001 (P208.01). |
Reduce dynamic performance of the load profile. Check mains voltage. Check settings for brake energy 0x2541:001 (P706.01) = [0]: Connect brake resistor to the power unit and activate the integrated brake chopper |
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
Operation on uninterrupted 1x230V current supply (UPS) has been activated: Only a reduced output current is provided. |
Switch back to operation with regular mains voltage |
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
Mains phase failure |
|
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
DC bus voltage is lower than specified in C0173. |
|
cawc |
| Cause | Remedy | Severity/response |
|---|---|---|
Braking energy is too high. (DC−bus voltage is higher than set in C0173.) |
|