Skip to main content

i550 motec

The i550 motec frequency inverter for wall mounting and motor mounting in protection class IP66 (UL Type 4X indoor) is the optimal decentralized drive solution. The inverter can be extended for universal use with an extension box with disconnect switch with/without Type E combination motor controller and operating elements.
Fast mounting and easy commissioning thanks to user-friendly tools as well as connections for commercially available connectors are the focus of this inverter. Parameters, drive behavior and usability correspond to our proven frequency inverters. Rounded off by high energy efficiency, we thus offer a modern and sustainable drive solution.
The requirements of the Ecodesign Directive, Standard EN IEC 61800-9-2, are met.
Application areas: Conveyor drives, traveling drives, winding drives, hoist drives, extruders, packaging machines, pumps, fans, ...

Highlights

  • Compact solution for decentralized drive technology, wall-mounted or motor-mounted, with high protection class IP66 (UL Type 4X indoor)
  • Wall-mounted expandable: Extension box with disconnect switch with/without Type E combination motor controller and operating elements
  • Fast mounting due to pluggable, standardized connections (plug & play)
  • Four IO-Link ports with limited IO-Link master functionality for easy data exchange between IO-Link sensors and actuators
  • Integrated regenerative module for very high energy efficiency - a brake resistor is no longer required
Image
    Fault ID: 0016
    Hex: 0016
    Description: I2xt overload
    Keypad display: OC6
    Cause Remedy Severity/response
    • Frequent and too long acceleration processes with motor overcurrent.
    • Permanent motor overload with Imotor >Irmotor

    Check drive dimensioning.

    Fault ID: x018
    Hex: x018
    Description: I2xt overload advance warning
    Keypad display: OC8
    Cause Remedy Severity/response
    • Frequent and too long acceleration processes with motor overcurrent.
    • Permanent motor overload with Imotor >Irmotor

    Check drive dimensioning.

    Fault ID: 0015
    Hex: 0015
    Description: I x t overload
    Keypad display: OC5
    Cause Remedy Severity/response
    • Frequent and too long acceleration with overcurrent
    • Continuous overload with Imotor > 1.05 x Irx

    Check drive dimensioning.

    Fault ID: 0012
    Hex: 0012
    Description: Motor cable earth fault
    Keypad display: OC2
    Cause Remedy Severity/response

    One of the motor phases has
    earth contact.

    • Search for cause of short circuit.
    • Check motor cable.
    Fault ID: 0011
    Hex: 0011
    Description: Short circuit of motor cable
    Keypad display: OC1
    Cause Remedy Severity/response

    Short circuit

    Excessive capacitive charging
    current in the motor cable.

    • Search for cause of short circuit.
    • Check motor cable.

      Use motor cable which is shorter