Sari la conținutul principal

i550 motec

The i550 motec frequency inverter for wall mounting and motor mounting in protection class IP66 (UL Type 4X indoor) is the optimal decentralized drive solution. The inverter can be extended for universal use with an extension box with disconnect switch with/without Type E combination motor controller and operating elements.
Fast mounting and easy commissioning thanks to user-friendly tools as well as connections for commercially available connectors are the focus of this inverter. Parameters, drive behavior and usability correspond to our proven frequency inverters. Rounded off by high energy efficiency, we thus offer a modern and sustainable drive solution.
The requirements of the Ecodesign Directive, Standard EN IEC 61800-9-2, are met.
Application areas: Conveyor drives, traveling drives, winding drives, hoist drives, extruders, packaging machines, pumps, fans, ...

Highlights

  • Compact solution for decentralized drive technology, wall-mounted or motor-mounted, with high protection class IP66 (UL Type 4X indoor)
  • Wall-mounted expandable: Extension box with disconnect switch with/without Type E combination motor controller and operating elements
  • Fast mounting due to pluggable, standardized connections (plug & play)
  • Four IO-Link ports with limited IO-Link master functionality for easy data exchange between IO-Link sensors and actuators
  • Integrated regenerative module for very high energy efficiency - a brake resistor is no longer required
Imagine
    Fault ID: 12816
    Hex: 0x3210
    Description: Fault - DC bus overvoltage
    Keypad display: DC Bus OV
    Cause Remedy Severity/response

    DC-bus voltage has exceeded the error threshold for overvoltage due to a too high braking energy or a too high mains voltage. The error threshold (display in 0x2540:006 (P208.06) results from the setting of the rated mains voltage in 0x2540:001 (P208.01).

    Reduce dynamic performance of the load profile.

    Check mains voltage.

    Check settings for brake energy
    management.

    0x2541:001 (P706.01) = [0]: Connect brake resistor to the power unit and activate the integrated brake chopper

    Fault

    Fault ID: 12672
    Hex: 0x3180
    Description: UPS operation active
    Keypad display: UPS oper. active
    Cause Remedy Severity/response

    Operation on uninterrupted 1x230V current supply (UPS) has been activated: Only a reduced output current is provided.

    Switch back to operation with regular mains voltage

    Warning

    Fault ID: 12576
    Hex: 0x3120
    Description: Mains phase fault 
    Keypad display: Mains Phase fail
    Cause Remedy Severity/response

    Mains phase failure

    • Check wiring of the mains connection.
    • Check fuses.

    Fault

    Fault ID: 1030
    Hex: 1030
    Description: Undervoltage in the DC bus
    Keypad display: LU
    Cause Remedy Severity/response

    DC bus voltage is lower than specified in C0173.

    • Check mains voltage
    • Check supply cable

    cawc

    Fault ID: 1020
    Hex: 1020
    Description: Overvoltage in DC bus
    Keypad display: OU
    Cause Remedy Severity/response

    Braking energy is too high. (DC−bus voltage is higher than set in C0173.)

    • Use braking unit or regenerative module.
    • Check dimensioning of the brake resistance.