    Fault ID: 0016
    Hex: 0016
    Description: I2xt overload
    Keypad display: OC6
    Cause Remedy Severity/response
    • Frequent and too long acceleration processes with motor overcurrent.
    • Permanent motor overload with Imotor >Irmotor

    Check drive dimensioning.

    Fault ID: x018
    Hex: x018
    Description: I2xt overload advance warning
    Keypad display: OC8
    Cause Remedy Severity/response
    • Frequent and too long acceleration processes with motor overcurrent.
    • Permanent motor overload with Imotor >Irmotor

    Check drive dimensioning.

    Fault ID: 0015
    Hex: 0015
    Description: I x t overload
    Keypad display: OC5
    Cause Remedy Severity/response
    • Frequent and too long acceleration with overcurrent
    • Continuous overload with Imotor > 1.05 x Irx

    Check drive dimensioning.

    Fault ID: 0012
    Hex: 0012
    Description: Motor cable earth fault
    Keypad display: OC2
    Cause Remedy Severity/response

    One of the motor phases has
    earth contact.

    • Search for cause of short circuit.
    • Check motor cable.
    Fault ID: 0011
    Hex: 0011
    Description: Short circuit of motor cable
    Keypad display: OC1
    Cause Remedy Severity/response

    Short circuit

    Excessive capacitive charging
    current in the motor cable.

    • Search for cause of short circuit.
    • Check motor cable.

      Use motor cable which is shorter
      or of lower capacitance.