Direkt zum Inhalt

i510 protec

The i510 protec frequency inverter uses the same tried-and-tested technology used in our control cabinet inverters. It only differs in terms of an adapted design. If there is not enough space in the control cabinet or the inverter has to be mounted directly on the motor in various machine modules, then this versatile and reliable device is the right solution.
The requirements of the Ecodesign Directive, Standard EN IEC 61800-9-2, are met.
Application areas: Conveyor drives, traveling drives, pumps, fans, ...

Highlights

  • Versions with keypad, USB module or WLAN module for easy commissioning
  • Industry standard fieldbus network options
Bild
    Fault ID: 12816
    Hex: 0x3210
    Description: Fault - DC bus overvoltage
    Keypad display: DC Bus OV
    Cause Remedy Severity/response

    DC-bus voltage has exceeded the error threshold for overvoltage due to a too high braking energy or a too high mains voltage. The error threshold (display in 0x2540:006 (P208.06) results from the setting of the rated mains voltage in 0x2540:001 (P208.01).

    Reduce dynamic performance of the load profile.

    Check mains voltage.

    Check settings for brake energy
    management.

    0x2541:001 (P706.01) = [0]: Connect brake resistor to the power unit and activate the integrated brake chopper

    Fault

    Fault ID: 12672
    Hex: 0x3180
    Description: UPS operation active
    Keypad display: UPS oper. active
    Cause Remedy Severity/response

    Operation on uninterrupted 1x230V current supply (UPS) has been activated: Only a reduced output current is provided.

    Switch back to operation with regular mains voltage

    Warning

    Fault ID: 12576
    Hex: 0x3120
    Description: Mains phase fault 
    Keypad display: Mains Phase fail
    Cause Remedy Severity/response

    Mains phase failure

    • Check wiring of the mains connection.
    • Check fuses.

    Fault

    Fault ID: 1030
    Hex: 1030
    Description: Undervoltage in the DC bus
    Keypad display: LU
    Cause Remedy Severity/response

    DC bus voltage is lower than specified in C0173.

    • Check mains voltage
    • Check supply cable

    cawc

    Fault ID: 1020
    Hex: 1020
    Description: Overvoltage in DC bus
    Keypad display: OU
    Cause Remedy Severity/response

    Braking energy is too high. (DC−bus voltage is higher than set in C0173.)

    • Use braking unit or regenerative module.
    • Check dimensioning of the brake resistance.