Direkt zum Inhalt

i510 protec

The i510 protec frequency inverter uses the same tried-and-tested technology used in our control cabinet inverters. It only differs in terms of an adapted design. If there is not enough space in the control cabinet or the inverter has to be mounted directly on the motor in various machine modules, then this versatile and reliable device is the right solution.
The requirements of the Ecodesign Directive, Standard EN IEC 61800-9-2, are met.
Application areas: Conveyor drives, traveling drives, pumps, fans, ...

Highlights

  • Versions with keypad, USB module or WLAN module for easy commissioning
  • Industry standard fieldbus network options
Bild
    Fault ID: 0016
    Hex: 0016
    Description: I2xt overload
    Keypad display: OC6
    Cause Remedy Severity/response
    • Frequent and too long acceleration processes with motor overcurrent.
    • Permanent motor overload with Imotor >Irmotor

    Check drive dimensioning.

    Fault ID: x018
    Hex: x018
    Description: I2xt overload advance warning
    Keypad display: OC8
    Cause Remedy Severity/response
    • Frequent and too long acceleration processes with motor overcurrent.
    • Permanent motor overload with Imotor >Irmotor

    Check drive dimensioning.

    Fault ID: 0015
    Hex: 0015
    Description: I x t overload
    Keypad display: OC5
    Cause Remedy Severity/response
    • Frequent and too long acceleration with overcurrent
    • Continuous overload with Imotor > 1.05 x Irx

    Check drive dimensioning.

    Fault ID: 0012
    Hex: 0012
    Description: Motor cable earth fault
    Keypad display: OC2
    Cause Remedy Severity/response

    One of the motor phases has
    earth contact.

    • Search for cause of short circuit.
    • Check motor cable.
    Fault ID: 0011
    Hex: 0011
    Description: Short circuit of motor cable
    Keypad display: OC1
    Cause Remedy Severity/response

    Short circuit

    Excessive capacitive charging
    current in the motor cable.

    • Search for cause of short circuit.
    • Check motor cable.

      Use motor cable which is shorter
      or of lower capacitance.