Перейти до основного вмісту

0x2350

Remedy

Check drive sizing.

  • Check machine/driven mechanics for excessive load.
  • Check settings of the motor data.
  • Reduce values for slip compensation 0x2B09:001 (P315.01), 0x2B09:002 (P315.02) and oscillation damping 0x2B0A:001 (P318.01), 0x2B0A:002 (P318.02).
Cause

Motor thermally overloaded, e. g. by an impermissible continuous current or by frequent or too long acceleration processes.

Description

CiA: i²xt overload (thermal state)

Keypad display

i2t motor

Fault message ID
9040
Severity/response

Fault (configurable)

  • The event can only be reset after a blocking time.
Severity/response - 1

Blocking time: 2 s

Severity/response - 2

Setting parameters: 0x2D4B:003 (P308.03)

Frequency inverter type