i550

0x3210

Remedy

Reduce dynamic performance of the load profile.

Check mains voltage.

Check settings for brake energy
management.

0x2541:001 (P706.01) = [0]: Connect brake resistor to the power unit and activate the integrated brake chopper

Cause

DC-bus voltage has exceeded the error threshold for overvoltage due to a too high braking energy or a too high mains voltage. The error threshold (display in 0x2540:006 (P208.06) results from the setting of the rated mains voltage in 0x2540:001 (P208.01).

Description

Fault - DC bus overvoltage

Keypad display
DC Bus OV
Fault message ID
12816
Severity/response

Fault

Frequency inverter type

0x3180

Remedy

Switch back to operation with regular mains voltage

Cause

Operation on uninterrupted 1x230V current supply (UPS) has been activated: Only a reduced output current is provided.

Description

UPS operation active

Keypad display
UPS oper. active
Fault message ID
12672
Severity/response

Warning

Frequency inverter type

0x3120

Remedy
  • Check wiring of the mains connection.
  • Check fuses.
Cause

Mains phase failure

Description

Mains phase fault 

Keypad display
Mains Phase fail
Fault message ID
12576
Severity/response

Fault

Frequency inverter type

0x2382

Remedy

Check drive sizing. 

  • Reduce the maximum current of the inverter 0x6073 (P324.00). 
  • In case of high mass inertias, reduce maximum current of the inverter 0x6073 (P324.00) to 150 %.
Cause

Device utilisation (ixt) too high by frequent and too long acceleration processes.

Description

Fault - Device utilization (ixt) too high

Keypad display

Ixt error

Fault message ID
9090
Severity/response

Fault (configurable)

  • The event can only be reset after a blocking time.
Severity/response - 1

Blocking time: 2 s

Severity/response - 2

Setting parameters: 0x2D40:005 (P135.05)

Frequency inverter type

0x2350

Remedy

Check drive sizing.

  • Check machine/driven mechanics for excessive load.
  • Check settings of the motor data.
  • Reduce values for slip compensation 0x2B09:001 (P315.01), 0x2B09:002 (P315.02) and oscillation damping 0x2B0A:001 (P318.01), 0x2B0A:002 (P318.02).
Cause

Motor thermally overloaded, e. g. by an impermissible continuous current or by frequent or too long acceleration processes.

Description

CiA: i²xt overload (thermal state)

Keypad display

i2t motor

Fault message ID
9040
Severity/response

Fault (configurable)

  • The event can only be reset after a blocking time.
Severity/response - 1

Blocking time: 2 s

Severity/response - 2

Setting parameters: 0x2D4B:003 (P308.03)

Frequency inverter type

0x2340

Remedy

Check motor cable for short circuit.

Cause

Short circuit of motor cable

Description

Short circuit at the motor end

Keypad display

Motor shorted

Fault message ID
9024
Severity/response

Fault

  • The inverter is disabled immediately. The motor has no torque (is coasting).
  • The event can only be reset after a blocking time.
Severity/response - 1

Blocking time: 2 s

Frequency inverter type

0x2320

Remedy
  • Check motor cable.
  • Check length of the motor cable.
  • Use shorter or lower-capacitance motor cable.
Cause
  • Short circuit/earth fault of motor cable
  • Capacitive charging current of the motor cable too high.
Description

Short circuit or earth leakage at the motor end

Keypad display

Earth leak

Fault message ID
8992
Severity/response

Fault

  • The inverter is disabled immediately. The motor has no torque (is coasting).
  • The event can only be reset after a blocking time.
Severity/response - 1

Blocking time: 2 s

Frequency inverter type

0x2250

Remedy
  • Check motor and wiring for short circuits.
  • Check brake resistor and wiring.
  • Check motor switching.
  • Check settings of the motor data.
Cause
  • Continuous overcurrent on the inverter/ motor side.
  • Overcurrent at the brake chopper (brake transistor).
  • DC bus relay has not been closed due to a malfunction.
Description

CiA: Continuous over current (internal)

Keypad display

PU over current

Fault message ID
8784
Severity/response

Fault

  • The inverter is disabled immediately. The motor has no torque (is coasting).
  • The event can only be reset after a blocking time.
Severity/response - 1

Blocking time: 2 s

Frequency inverter type