0x3210

Remedy

Reduce dynamic performance of the load profile.

Check mains voltage.

Check settings for brake energy
management.

0x2541:001 (P706.01) = [0]: Connect brake resistor to the power unit and activate the integrated brake chopper

Cause

DC-bus voltage has exceeded the error threshold for overvoltage due to a too high braking energy or a too high mains voltage. The error threshold (display in 0x2540:006 (P208.06) results from the setting of the rated mains voltage in 0x2540:001 (P208.01).

Description

Fault - DC bus overvoltage

Keypad display
DC Bus OV
Fault message ID
12816
Severity/response

Fault

Frequency inverter type

0x3180

Remedy

Switch back to operation with regular mains voltage

Cause

Operation on uninterrupted 1x230V current supply (UPS) has been activated: Only a reduced output current is provided.

Description

UPS operation active

Keypad display
UPS oper. active
Fault message ID
12672
Severity/response

Warning

Frequency inverter type

0x3120

Remedy
  • Check wiring of the mains connection.
  • Check fuses.
Cause

Mains phase failure

Description

Mains phase fault 

Keypad display
Mains Phase fail
Fault message ID
12576
Severity/response

Fault

Frequency inverter type

0x2382

Remedy

Check drive sizing. 

  • Reduce the maximum current of the inverter 0x6073 (P324.00). 
  • In case of high mass inertias, reduce maximum current of the inverter 0x6073 (P324.00) to 150 %.
Cause

Device utilisation (ixt) too high by frequent and too long acceleration processes.

Description

Fault - Device utilization (ixt) too high

Keypad display

Ixt error

Fault message ID
9090
Severity/response

Fault (configurable)

  • The event can only be reset after a blocking time.
Severity/response - 1

Blocking time: 2 s

Severity/response - 2

Setting parameters: 0x2D40:005 (P135.05)

Frequency inverter type