0x6402 Manufacturer Lenze Product category i550 Parameter Motor type Data type U16 Default setting Squirrel cage induction [7] M - A P Fieldbus MCTRL Factor 1
0x2D67:002 Manufacturer Lenze Product category i550 Parameter Maximum torque monitoring: Triggering delay Data type U16 Default setting 0.000 s M - A P Fieldbus MCTRL Display Code P329.02 Factor 1000
0x2D67:001 Manufacturer Lenze Product category i550 Parameter Maximum torque monitoring: Response Data type U8 Default setting No response [0] M - A P Fieldbus MCTRL Display Code P329.01 Factor 1
0x2D4B:002 Manufacturer Lenze Product category i550 Parameter Motor overload monitoring (i²xt): Speed compensation Data type U8 Default setting On [0] M - A P Fieldbus MCTRL Display Code P308.02 Factor 1
0x2D4B:001 Manufacturer Lenze Product category i550 Parameter Motor overload monitoring (i²xt): Maximum utilisation [60 s] Data type U16 Default setting 150 % M - A P Fieldbus MCTRL Display Code P308.01 Factor 1
0x2C13 Manufacturer Lenze Product category i550 Parameter SLSM-PSM low speed method Data type U8 Default setting Carrier based [1] M - A P Fieldbus MCTRL Factor 1
0x2C12:002 Manufacturer Lenze Product category i550 Parameter SM low speed range: Standstill current Data type U16 Default setting 30 % M - A P Fieldbus MCTRL Factor 1
0x2C12:001 Manufacturer Lenze Product category i550 Parameter SM low speed range: Acceleration current Data type U16 Default setting 70 % M - A P Fieldbus MCTRL Factor 1
0x2C11:006 Manufacturer Lenze Product category i550 Parameter High speed range: Stall monitoring limit Data type U16 Default setting 50 % M - A P Fieldbus MCTRL Factor 1
0x2C11:004 Manufacturer Lenze Product category i550 Parameter High speed range: Tracking controller decouple time Data type U16 Default setting 200.0 ms M - A P Fieldbus MCTRL Factor 10